Backflow assembly test: 9716 Hickory Ln

Approved

Filed May 18, 2025 by Sam Brandt, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
May 18, 2025
Assembly type
RP
Serial number
W199567
Size
1
Test gauge serial
G-4302
Gauge calibration date
Sep 14, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 001-44-01189
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9716 Hickory Ln
Owner: Morgan Whitcomb
Parcel 001-44-01189