Backflow assembly test: 215 Laurel Way

Approved

Filed May 22, 2026 by Riley Danner, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
May 22, 2026
Assembly type
PVB
Serial number
W144901
Size
3/4
Test gauge serial
G-3529
Gauge calibration date
Apr 12, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Danner, current on the service date
  • All required fields present
  • Address matches parcel 001-53-01032
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

215 Laurel Way
Owner: Emerson Ellery
Parcel 001-53-01032