Backflow assembly test: 2792 Pine Knoll Way

Approved

Filed Aug 12, 2025 by Avery Ellery, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Aug 12, 2025
Assembly type
RP
Serial number
K198876
Size
1
Test gauge serial
G-6619
Gauge calibration date
Feb 5, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ellery, current on the service date
  • All required fields present
  • Address matches parcel 001-94-01224
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2792 Pine Knoll Way
Owner: Alex Danner
Parcel 001-94-01224