Backflow assembly test: 707 Orchard Ct

Approved

Filed Dec 11, 2023 by Rowan Okafor, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Dec 11, 2023
Assembly type
RP
Serial number
Z161731
Size
3/4
Test gauge serial
G-6466
Gauge calibration date
Apr 17, 2023
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 001-56-01257
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

707 Orchard Ct
Owner: Cameron Danner
Parcel 001-56-01257