Back to the backflow review queue

Backflow assembly test: Crossroads Grill

Approved

Filed Oct 10, 2024 by Sam Brandt, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 10, 2024
Assembly type
DC
Serial number
B105681
Size
4
Test gauge serial
G-3219
Gauge calibration date
Apr 22, 2024
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 001-22-01340
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8556 Orchard Ln
Owner: Fairley Holdings LLC
Parcel 001-22-01340