Back to the backflow review queue

Backflow assembly test: 9118 Fox Run Trl

Approved

Filed Jun 10, 2023 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 10, 2023
Assembly type
DC
Serial number
Z906524
Size
1
Test gauge serial
G-7271
Gauge calibration date
Nov 23, 2022
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-74-01248
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9118 Fox Run Trl
Owner: Casey Stroud
Parcel 001-74-01248