Backflow assembly test: 5273 Old Church Dr

Approved

Filed Apr 8, 2025 by Riley Danner, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 8, 2025
Assembly type
RP
Serial number
A167281
Size
1
Test gauge serial
G-9185
Gauge calibration date
Jun 19, 2024
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Danner, current on the service date
  • All required fields present
  • Address matches parcel 001-47-01250
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5273 Old Church Dr
Owner: Hayden Ashby
Parcel 001-47-01250