Backflow assembly test: 9487 Fox Run Way

Approved

Filed May 1, 2024 by Rowan Okafor, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
May 1, 2024
Assembly type
DC
Serial number
A500161
Size
3/4
Test gauge serial
G-2059
Gauge calibration date
Aug 12, 2023
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 001-95-01313
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.