Backflow assembly test: 2402 Mill Creek Dr

Approved

Filed May 28, 2025 by Quinn Nguyen, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
May 28, 2025
Assembly type
RP
Serial number
Z877369
Size
1
Test gauge serial
G-5686
Gauge calibration date
Feb 8, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 001-42-01076
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.