Backflow assembly test: 5645 Ridgeview Rd
ApprovedFiled Nov 1, 2024 by Avery Ellery, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 1, 2024
- Assembly type
- RP
- Serial number
- B827817
- Size
- 3/4
- Test gauge serial
- G-3269
- Gauge calibration date
- Apr 27, 2024
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ellery, current on the service date
- All required fields present
- Address matches parcel 001-69-01088
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.