Backflow assembly test: 8158 Mill Creek Ct
ApprovedFiled Sep 25, 2025 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 25, 2025
- Assembly type
- DC
- Serial number
- Z627036
- Size
- 3/4
- Test gauge serial
- G-4863
- Gauge calibration date
- Jul 28, 2025
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 143-69-01159
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8158 Mill Creek Ct
Owner: Morgan Calloway
Parcel 143-69-01159