Backflow assembly test: Maple Leaf Market

Approved

Filed Sep 1, 2026 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Sep 1, 2026
Assembly type
DC
Serial number
Z958156
Size
4
Test gauge serial
G-9709
Gauge calibration date
Apr 14, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-99-01076
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.