Backflow assembly test: 3273 Cedar Hollow Ln

Approved

Filed Oct 7, 2025 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Oct 7, 2025
Assembly type
RP
Serial number
Z678882
Size
1
Test gauge serial
G-8320
Gauge calibration date
Mar 4, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-27-01224
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3273 Cedar Hollow Ln
Owner: Cameron Danner
Parcel 143-27-01224