Backflow assembly test: 4811 Spring Branch Ct

Approved

Filed May 31, 2025 by Blake Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 31, 2025
Assembly type
RP
Serial number
A142597
Size
1
Test gauge serial
G-4625
Gauge calibration date
Feb 11, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Wexler, current on the service date
  • All required fields present
  • Address matches parcel 143-30-01143
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4811 Spring Branch Ct
Owner: Alex Nguyen
Parcel 143-30-01143