Backflow assembly test: 9544 Fox Run Rd

Approved

Filed Oct 22, 2025 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Oct 22, 2025
Assembly type
DC
Serial number
B312746
Size
3/4
Test gauge serial
G-4656
Gauge calibration date
Jan 28, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-62-01202
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.