Backflow assembly test: 4811 Spring Branch Ct
ApprovedFiled Jun 30, 2023 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 30, 2023
- Assembly type
- RP
- Serial number
- A142597
- Size
- 1
- Test gauge serial
- G-4548
- Gauge calibration date
- Jan 29, 2023
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 143-30-01143
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.