Filed Mar 15, 2026 by Taylor Pruitt, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Mar 15, 2026
Assembly type
PVB
Serial number
A196512
Size
1
Test gauge serial
G-6189
Gauge calibration date
Jun 10, 2025
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 143-47-01277
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7211 Sycamore Ct
Owner: Avery Brandt
Parcel 143-47-01277