Back to the backflow review queue

Backflow assembly test: Golden Taqueria

Approved

Filed Jul 30, 2025 by Blake Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 30, 2025
Assembly type
RP
Serial number
Z264814
Size
1 1/2
Test gauge serial
G-4835
Gauge calibration date
Dec 6, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Wexler, current on the service date
  • All required fields present
  • Address matches parcel 143-79-01128
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7994 Sycamore Way
Owner: Harlow Holdings LLC
Parcel 143-79-01128