Back to the backflow review queue
Backflow assembly test: 9477 Cedar Hollow Ln
ApprovedFiled Jun 30, 2026 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 30, 2026
- Assembly type
- RP
- Serial number
- W647640
- Size
- 1
- Test gauge serial
- G-1201
- Gauge calibration date
- Oct 27, 2025
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 143-58-01105
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9477 Cedar Hollow Ln
Owner: Taylor Okafor
Parcel 143-58-01105