Backflow assembly test: 9558 Stone Gate Dr
ApprovedFiled Jan 9, 2026 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Jan 9, 2026
- Assembly type
- DC
- Serial number
- B304765
- Size
- 1
- Test gauge serial
- G-5157
- Gauge calibration date
- Oct 8, 2025
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 143-93-01033
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.