Backflow assembly test: Golden Grill

Approved

Filed Sep 17, 2023 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Sep 17, 2023
Assembly type
DC
Serial number
K109991
Size
4
Test gauge serial
G-2500
Gauge calibration date
Apr 8, 2023
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-80-01236
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2689 Sycamore Dr
Owner: Ashby Holdings LLC
Parcel 143-80-01236