Backflow assembly test: Main Street Bakery

Approved

Filed Jul 14, 2024 by Jamie Benton, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 14, 2024
Assembly type
RP
Serial number
A678381
Size
1
Test gauge serial
G-4558
Gauge calibration date
Mar 31, 2024
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Benton, current on the service date
  • All required fields present
  • Address matches parcel 143-97-01319
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.