Back to the backflow review queue

Backflow assembly test: 7734 Meadow Lark Rd

Approved

Filed Apr 25, 2025 by Reese Fairley, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 25, 2025
Assembly type
DC
Serial number
W604114
Size
3/4
Test gauge serial
G-3504
Gauge calibration date
Oct 6, 2024
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-24-01188
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7734 Meadow Lark Rd
Owner: Sam Pruitt
Parcel 143-24-01188