Backflow assembly test: 5719 Sycamore Dr
ApprovedFiled Jun 16, 2024 by Hayden Okafor, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 16, 2024
- Assembly type
- RP
- Serial number
- W100095
- Size
- 1
- Test gauge serial
- G-6018
- Gauge calibration date
- Feb 11, 2024
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Okafor, current on the service date
- All required fields present
- Address matches parcel 131-79-01299
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.