Backflow assembly test: 1831 Hickory Rd

Approved

Filed Nov 19, 2025 by Hayden Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Nov 19, 2025
Assembly type
RP
Serial number
B250988
Size
3/4
Test gauge serial
G-2475
Gauge calibration date
Jul 27, 2025
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-60-01012
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.