Back to the backflow review queue
Backflow assembly test: Maple Leaf Self Storage
ApprovedFiled Nov 2, 2026 by Hayden Pruitt, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 2, 2026
- Assembly type
- RP
- Serial number
- A749539
- Size
- 1 1/2
- Test gauge serial
- G-7178
- Gauge calibration date
- Feb 13, 2026
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Pruitt, current on the service date
- All required fields present
- Address matches parcel 131-92-01178
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1986 Spring Branch Trl
Owner: Whitcomb Holdings LLC
Parcel 131-92-01178