Backflow assembly test: 443 Meadow Lark Dr

Approved

Filed Oct 29, 2026 by Hayden Pruitt, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Oct 29, 2026
Assembly type
PVB
Serial number
A416959
Size
3/4
Test gauge serial
G-3742
Gauge calibration date
May 9, 2026
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 131-14-01057
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

443 Meadow Lark Dr
Owner: Emerson Fairley
Parcel 131-14-01057