Backflow assembly test: 4519 Mill Creek Rd

Approved

Filed Nov 23, 2023 by Hayden Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Nov 23, 2023
Assembly type
RP
Serial number
W641417
Size
3/4
Test gauge serial
G-5797
Gauge calibration date
Mar 3, 2023
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-17-01202
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4519 Mill Creek Rd
Owner: Reese Pruitt
Parcel 131-17-01202