Back to the backflow review queue

Backflow assembly test: Corner Medical Offices

Approved

Filed Jun 19, 2026 by Hayden Pruitt, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jun 19, 2026
Assembly type
RP
Serial number
K221894
Size
2
Test gauge serial
G-3657
Gauge calibration date
Mar 30, 2026
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 131-41-01195
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1678 Spring Branch Trl
Owner: Harlow Holdings LLC
Parcel 131-41-01195