Backflow assembly test: 1962 Sycamore Dr

Approved

Filed Sep 24, 2024 by Parker Ashby, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 24, 2024
Assembly type
PVB
Serial number
W847925
Size
3/4
Test gauge serial
G-6563
Gauge calibration date
Dec 17, 2023
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 131-22-01019
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.