Backflow assembly test: Maple Leaf Brewing Co
ApprovedFiled Nov 2, 2024 by Emerson Benton, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 2, 2024
- Assembly type
- RP
- Serial number
- W729058
- Size
- 2
- Test gauge serial
- G-1479
- Gauge calibration date
- Jan 26, 2024
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Benton, current on the service date
- All required fields present
- Address matches parcel 131-36-01083
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3133 Turkey Hill Rd
Owner: Brandt Holdings LLC
Parcel 131-36-01083