Backflow assembly test: 4763 Old Church Way

Approved

Filed May 10, 2025 by Emerson Benton, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 10, 2025
Assembly type
RP
Serial number
A302852
Size
1
Test gauge serial
G-6856
Gauge calibration date
Nov 23, 2024
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Benton, current on the service date
  • All required fields present
  • Address matches parcel 131-38-01237
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.