Backflow assembly test: 3726 Laurel Way
ApprovedFiled Sep 12, 2024 by Logan Okafor, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 12, 2024
- Assembly type
- RP
- Serial number
- W976591
- Size
- 1
- Test gauge serial
- G-8603
- Gauge calibration date
- Mar 5, 2024
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Okafor, current on the service date
- All required fields present
- Address matches parcel 131-40-01297
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.