ApprovedFiled Sep 21, 2026 by Reese Ellery, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 21, 2026
- Assembly type
- PVB
- Serial number
- A697348
- Size
- 1
- Test gauge serial
- G-7789
- Gauge calibration date
- Jul 11, 2026
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Ellery, current on the service date
- All required fields present
- Address matches parcel 045-33-01318
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.