Backflow assembly test: 1075 Ridgeview Rd
ApprovedFiled Aug 15, 2025 by Drew Vance, Clearwater Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 15, 2025
- Assembly type
- RP
- Serial number
- W709813
- Size
- 3/4
- Test gauge serial
- G-1732
- Gauge calibration date
- Jun 12, 2025
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 045-49-01239
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.