Backflow assembly test: 2623 Cedar Hollow Dr

Approved

Filed Feb 12, 2025 by Drew Vance, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 12, 2025
Assembly type
RP
Serial number
B770108
Size
3/4
Test gauge serial
G-9990
Gauge calibration date
Jul 8, 2024
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
1.2 psid
Relief valve opened at
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 045-96-01211
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2623 Cedar Hollow Dr
Owner: Drew Lindqvist
Parcel 045-96-01211