Backflow assembly test: Main Street Brewing Co

Approved

Filed Sep 27, 2026 by Cameron Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 27, 2026
Assembly type
DC
Serial number
W276794
Size
1 1/2
Test gauge serial
G-7650
Gauge calibration date
Jul 11, 2026
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 045-46-01313
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5978 Turkey Hill Way
Owner: Kessler Holdings LLC
Parcel 045-46-01313