Backflow assembly test: 4783 Spring Branch Ct

Approved

Filed Aug 26, 2025 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 26, 2025
Assembly type
RP
Serial number
W964406
Size
3/4
Test gauge serial
G-4847
Gauge calibration date
Sep 17, 2024
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ellery, current on the service date
  • All required fields present
  • Address matches parcel 045-94-01224
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.