Backflow assembly test: Riverside Apartments
ApprovedFiled Jul 29, 2025 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 29, 2025
- Assembly type
- RP
- Serial number
- K445404
- Size
- 1
- Test gauge serial
- G-9098
- Gauge calibration date
- Apr 7, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Ellery, current on the service date
- All required fields present
- Address matches parcel 045-89-01197
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
1080 Pine Knoll Ln
Owner: Vance Holdings LLC
Parcel 045-89-01197