Backflow assembly test: 8864 Stone Gate Trl
ApprovedFiled Oct 22, 2024 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 22, 2024
- Assembly type
- RP
- Serial number
- W572117
- Size
- 3/4
- Test gauge serial
- G-3459
- Gauge calibration date
- Apr 3, 2024
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Ellery, current on the service date
- All required fields present
- Address matches parcel 045-75-01049
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8864 Stone Gate Trl
Owner: Parker Brandt
Parcel 045-75-01049