Back to the backflow review queue
Backflow assembly test: 5603 Quarry Trl
ApprovedFiled Jul 28, 2024 by Cameron Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 28, 2024
- Assembly type
- DC
- Serial number
- B173437
- Size
- 3/4
- Test gauge serial
- G-5290
- Gauge calibration date
- Nov 2, 2023
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Whitcomb, current on the service date
- All required fields present
- Address matches parcel 045-28-01152
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5603 Quarry Trl
Owner: Sam Harlow
Parcel 045-28-01152