Backflow assembly test: 220 Spring Branch Way
ApprovedFiled Nov 19, 2025 by Emerson Brandt, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 19, 2025
- Assembly type
- RP
- Serial number
- A900000
- Size
- 3/4
- Test gauge serial
- G-4561
- Gauge calibration date
- May 29, 2025
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Brandt, current on the service date
- All required fields present
- Address matches parcel 007-13-01320
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.