Back to the backflow review queue

Backflow assembly test: 8360 Quarry Way

Approved

Filed Dec 23, 2024 by Parker Danner, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 23, 2024
Assembly type
DC
Serial number
A900677
Size
1
Test gauge serial
G-1271
Gauge calibration date
Mar 14, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Danner, current on the service date
  • All required fields present
  • Address matches parcel 007-53-01223
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8360 Quarry Way
Owner: Blake Hollins
Parcel 007-53-01223