Backflow assembly test: Blue Heron Dental

Approved

Filed Dec 6, 2024 by Sam Fairley, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 6, 2024
Assembly type
RP
Serial number
A544839
Size
2
Test gauge serial
G-6723
Gauge calibration date
Feb 17, 2024
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Fairley, current on the service date
  • All required fields present
  • Address matches parcel 007-36-01140
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.