Backflow assembly test: Two Rivers Medical Offices

Approved

Filed Jul 30, 2023 by Emerson Brandt, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 30, 2023
Assembly type
RP
Serial number
B529532
Size
1
Test gauge serial
G-4680
Gauge calibration date
Apr 13, 2023
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Brandt, current on the service date
  • All required fields present
  • Address matches parcel 007-88-01349
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7557 Meadow Lark Trl
Owner: Nguyen Holdings LLC
Parcel 007-88-01349