Backflow assembly test: 5718 Mill Creek Trl

Approved

Filed Nov 30, 2023 by Sam Fairley, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 30, 2023
Assembly type
RP
Serial number
K642069
Size
1
Test gauge serial
G-9014
Gauge calibration date
Jun 30, 2023
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Fairley, current on the service date
  • All required fields present
  • Address matches parcel 007-60-01162
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.