Backflow assembly test: Golden Diner
ApprovedFiled Apr 10, 2024 by Emerson Brandt, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Apr 10, 2024
- Assembly type
- RP
- Serial number
- B837086
- Size
- 1 1/2
- Test gauge serial
- G-2411
- Gauge calibration date
- Jan 21, 2024
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Brandt, current on the service date
- All required fields present
- Address matches parcel 007-30-01234
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.