Back to the backflow review queue

Backflow assembly test: 9563 Turkey Hill Dr

Filed Nov 21, 2026 by Parker Danner, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 21, 2026
Assembly type
RP
Serial number
A279302
Size
3/4
Test gauge serial
G-4247
Gauge calibration date
Oct 19, 2026
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Danner, current on the service date
  • All required fields present
  • Address matches parcel 007-32-01183
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

9563 Turkey Hill Dr
Owner: Jamie Harlow
Parcel 007-32-01183