Backflow assembly test: 1845 Pine Knoll Dr

Approved

Filed Mar 11, 2026 by Sam Fairley, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 11, 2026
Assembly type
DC
Serial number
A497032
Size
3/4
Test gauge serial
G-9914
Gauge calibration date
Mar 27, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Fairley, current on the service date
  • All required fields present
  • Address matches parcel 007-64-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1845 Pine Knoll Dr
Owner: Reese Whitcomb
Parcel 007-64-01256