Back to the backflow review queue
Backflow assembly test: 1247 Ridgeview Ln
ApprovedFiled Sep 1, 2026 by Emerson Brandt, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 1, 2026
- Assembly type
- RP
- Serial number
- Z431334
- Size
- 1
- Test gauge serial
- G-5307
- Gauge calibration date
- Nov 6, 2025
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Brandt, current on the service date
- All required fields present
- Address matches parcel 007-26-01239
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1247 Ridgeview Ln
Owner: Morgan Harlow
Parcel 007-26-01239